Permit: T07EL01971

Parcel: 131020780


Addresses:

5350 E 26TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01971

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING. CANNOT USE MINERALLAC STRAP. CONNECT BRACING NEAR TOP OF MAST. INSTALL 2 LEGS IN V SHAPE
2. PROPERLY IDENTIFY NEUTRALS FOR SUB-PANELS
NEC 200.6
3. WHY DOES SUB-PANEL #2 HAVE UNDERSIZED NEUTRAL & SOLID COPPER. IS THERE A SPLICE BEHIND SERVICE PANEL?
4. INSTALL NEW GROUND RODS FOR NEW SERVICE. DO NOT REUSE EXISTING. APPEARS ONE GROUND ROD HAS BEEN CUT.