Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01971
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING. CANNOT USE MINERALLAC STRAP. CONNECT BRACING NEAR TOP OF MAST. INSTALL 2 LEGS IN V SHAPE 2. PROPERLY IDENTIFY NEUTRALS FOR SUB-PANELS NEC 200.6 3. WHY DOES SUB-PANEL #2 HAVE UNDERSIZED NEUTRAL & SOLID COPPER. IS THERE A SPLICE BEHIND SERVICE PANEL? 4. INSTALL NEW GROUND RODS FOR NEW SERVICE. DO NOT REUSE EXISTING. APPEARS ONE GROUND ROD HAS BEEN CUT. |