Permit: T07EL01941

Parcel: 140241110


Addresses:

1367 E GINTER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 2 GROUND RODS REQUIRED 6' MIN. APART
2. GROUNDING ELECTRODE CONDUCTOR MUST TERMINATE ON NEUTRAL BAR
3. USE APPROVED STRAPS TO SUPPORT CONDUIT
4. FLEXIBLE CORD NOT PROPER WIRING METHOD TO HOUSE, USE CONDUIT & TERMINATE PROPERLY
5. WIRING AT PORCH LIGHT SOCKET NOT TO CODE ON EAST OUTSIDE
6. UNDERGROUND CONDUIT MUST BE 18" MIN. DEPTH, CONDUIT ON NORTH BACK WALL NOT SUPPORTED, LB COVER MISSING SCREW
7. POLE LIGHT ON EAST CORNER IS HANGING BY ROMEX
8. NEED ACCESS INSIDE, UNIT LOCKED

OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN OR LICENSED CONTR. TO DO WORK.