Permit: T07EL01940

Parcel: 125113400


Addresses:

921 N CHRYSLER DR 2

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PROPER CONNECTOR FOR EQUIPMENT GROUNDS SPLIT BOLTS ARE LISTED FOR CONNECTION OF ONLY TWO CONDUCTORS - NEC 110.3B
2. NEED PLASTIC BUSHING #4 & LARGER CONDUCTOR -
NEC 300.4F
3. EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119
4. SINGLE AND TWO GANG J-BOX COVERS TO BE REMOVABLE NOT CEMENTED SHUT
12/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*