Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROPER CONNECTOR FOR EQUIPMENT GROUNDS SPLIT BOLTS ARE LISTED FOR CONNECTION OF ONLY TWO CONDUCTORS - NEC 110.3B 2. NEED PLASTIC BUSHING #4 & LARGER CONDUCTOR - NEC 300.4F 3. EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119 4. SINGLE AND TWO GANG J-BOX COVERS TO BE REMOVABLE NOT CEMENTED SHUT |
|
| 12/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |