Permit: T07EL01927

Parcel: 135103780


Addresses:

7309 E 35TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/20/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DETAILED PANEL DIRECTORY AT HOUSE SUB-PANEL - NO ABBREVIATIONS NEC 408.4
2. CANNOT USE CHASE NIPPLE FOR CONNECTION OF LB TO PANEL. USE APPROVED FITTING NEC 110.3
3. MISSING COVER ON LB
4. PLEASE VERIFY PERMIT FOR NEW POOL. PROVIDE COPY OF PERMIT AT NEXT INSPECTION
5. SEAL OPENING IN BACK OF SUB-PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE MATERIAL
6. NEED TO PROVIDE 30" WIDE WORKING SPACE IN FRONT
OF SUB-PANEL