Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE DETAILED PANEL DIRECTORY AT HOUSE SUB-PANEL - NO ABBREVIATIONS NEC 408.4 2. CANNOT USE CHASE NIPPLE FOR CONNECTION OF LB TO PANEL. USE APPROVED FITTING NEC 110.3 3. MISSING COVER ON LB 4. PLEASE VERIFY PERMIT FOR NEW POOL. PROVIDE COPY OF PERMIT AT NEXT INSPECTION 5. SEAL OPENING IN BACK OF SUB-PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE MATERIAL 6. NEED TO PROVIDE 30" WIDE WORKING SPACE IN FRONT OF SUB-PANEL |