Permit: T07EL01920

Parcel: 126170130


Addresses:

4117 E PASEO DORADO

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL WEATHERPROOF BOXES
2. INSTALL WEATHERPROOF COVERS
3. UNCOVER ALL UNDERGROUND WIRING
4. INSTALL CONNECTORS WHERE PVC ENTERS BOXES
5. GROUND ALL METAL BOXES
6. PVC TO EXTEND 18" BELOW GRADE FOR PROTECTION OF UF CABLE
7. PROPERLY MAKE UP GROUND CONNECTIONS USE WIRE NUT OR CRIMP
8. GROUND ALL METAL BOXES
9. PROVIDE MIN. 6" OF FREE CONDUCTOR LENGTH IN JUNCTION BOXES
10. HAVE ELECTRICAL CONTRACTOR ON SITE FOR REMOVAL OF LIGHT FIXTURES
11. UF CABLE CANNOT BE EMBEDDED IN CONCRETE/CEMENT
PLAN CALLS FOR CONDUIT TO BE INSTALLED IN WALL
12. WAS GATE MOTOR PERMITTED
13. INDICATE NEW CIRCUITS AT PANEL
14. REMOVE KNOCKOUTS FOR BREAKERS INSTALLED
15. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL