Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01917
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ANCHOR BRACE SUPPORTS INTO JOIST NOT ROOF SHEATHING 2. FINISH #1 OF PREVIOUS INSPECTION 3. CHECK BONDING OF OTHER PIPING UNDER STRUCTURES |
|
10/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPOSITION SERVICE BUS TO OVERHEAD POSITION PER INSTRUCTION SHEET PROVIDED. NEC 110.3 2. CANNOT VERIFY GAS & WATER BOND - NEC 250.104 3. DOES THIS SERVICE FEED BOTH UNITS? 4. MAST BRACING TO BE POSITIONED IN OPPOSITE DIRECTION OF SERVICE DROP CONDUCTORS 5. PLEASE PROVIDE LADDER TO ACCESS JUNCTION BOX 6. MARK "SERVICE DISCONNECT" NEC 230.70 |