Permit: T07EL01915

Parcel: 133060730


Addresses:

8973 E CALLE PLAYA

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/26/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/15/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) COMPLETE ITEM #3 FROM PREVIOUS INSPECTION
2) OK GROUND RODS, WATER AND GAS BOND
3) INSTALL SHEET METAL ABOVE BREAKER POSITIONS HIGHER THAN 6'-7". THIS IS TO PREVENT INSTALLATION OF BREAKERS ALSO MARK THESE POSITIONS NOT TO BE USED
4) RECALL WHEN READY
11/13/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND RODS TO BE MINIMUM 6' APART NEC 250. HAVE EXPOSED FOR NEXT INSPECTION
2) CANNOT HAVE BREAKER POSITION HIGHER THAN 6'-7" NEC 240 & 408
3) CONNECT EQUIPMENT GROUNDING CONDUCTOR TO 8" X 8" JUNCTION BOX NEC 250
4) REMOVE PAINT AT GROUND CLAMP CONNECTION ON GAS PIPE NEC 250