Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/15/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEM #3 FROM PREVIOUS INSPECTION 2) OK GROUND RODS, WATER AND GAS BOND 3) INSTALL SHEET METAL ABOVE BREAKER POSITIONS HIGHER THAN 6'-7". THIS IS TO PREVENT INSTALLATION OF BREAKERS ALSO MARK THESE POSITIONS NOT TO BE USED 4) RECALL WHEN READY |
|
| 11/13/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MINIMUM 6' APART NEC 250. HAVE EXPOSED FOR NEXT INSPECTION 2) CANNOT HAVE BREAKER POSITION HIGHER THAN 6'-7" NEC 240 & 408 3) CONNECT EQUIPMENT GROUNDING CONDUCTOR TO 8" X 8" JUNCTION BOX NEC 250 4) REMOVE PAINT AT GROUND CLAMP CONNECTION ON GAS PIPE NEC 250 |