Permit: T07EL01909

Parcel: 13317062A

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) VERIFY ROOM WITH TREAD MILL AND EXAM TABLE
2) SUPPORT M/C ABOVE CEILING
3) LABEL NEW CIRCUITS PER 408.4
11/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
UNIT IS WIRED IN ROMEX AND DOES NOT MEET THE REQUIREMENTS OF 517.13
11/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*