Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | ELECTRIC - RECONNECT | Approved | ||
| 07/17/2008 | ELECTRIC - RECONNECT | Partial Approval | 1) STRAP GROUND WIRE BELOW SERVICE TO WALL 2) WEST LIV ROOM-PROVIDE FULL SIZE PROTECTION PLATE FOR ROMEX TO SWITCHES, ALSO BACK SW FOR MID-BEDROOM. USE LISTED FHA PROTECTOR PLATES WHERE 1 1/4" SPACE NOT AVAILABLE TO PROTECT ROMEX IN WALLS 3) PROVIDE A LADDER TO GET INTO ATTIC 4) OK TO CLEAR SERVICE RECN/INCREASE ONLY |
|
| 10/29/2007 | ELECTRIC - RECONNECT | Denied | ||
| 10/26/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |