Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE CORRECTION DATED 11/20/07 |
|
| 11/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE PERMIT T04EL01407 THAT NEEDS TO BE RE-OPENED INSPECTED AND APPROVED |
|
| 11/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MAIN HOUSE 1. AN APPROVED MAST BRACE IS NEEDED 2. SEAL OR REMOVE & SEAL ABOVE PANEL 3. NEED ACCESS 2ND UNIT 1. A MANUFACTURES HOLD DOWN IS NEEDED 2. GROUND SWITCHES 3. FINISH PREVIOUS ITEMS |
|
| 11/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 2ND STRUCTURE: 1. PROTECT CABLES AT PANEL & FILL UNUSED PORTION OF OPENING WITH NON-COMBUSTIBLE PRODUCT 2. A MAIN DISCONNECTING MEANS IS NEEDED 225.31 & 32 3. PLEASE VERIFY GROUNDING ELECTRODE SYSTEM, GAS AND WATER BONDS 4. EXPOSE NEW WIRING IN WALL TO INSPECT 5. PROPERLY MAKE UP GROUNDS WITH AN APPROVED SPLICE 6. GROUND METAL BOXES 7. PROTECT CONDUCTORS AT BATH FIXTURE - MAKE TO BE IN BOX 8. RECEPTACLE COVER TO BE AS PER 406.8 9. EXPOSED CONDUCTORS AT POOL EQUIPMENT MAIN UNIT: LOCKED NO ACCESS |
|
| 10/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* WHICH UNIT IS THIS INSPECTION FOR? WHERE IS PAPERWORK WITH VIOLATIONS? LOCKED NO ONE HERE NO ANSWER AT PHONE NUMBER |
|
| 10/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* GATE LOCKED |