Permit: T07EL01899

Parcel: 111082800


Addresses:

2742 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDUCTORS IN 1 1/4" RACEWAY TO BE DERATED FOR AMPACITY - NEC 310.15
2. NEED MINIMUM #10 CU GROUND TO J-BOX
ENCLOSURE - 250.122
3. PANEL DIRECTORY TO BE CORRECT & LEGIBLE - NEC 408.4
4. USE STRUT & CLAMPS FOR MAST ABOVE PANEL -
WOOD & LAGS NOT HOLDING - WOOD WILL ROT - NEC 230