Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUCTORS IN 1 1/4" RACEWAY TO BE DERATED FOR AMPACITY - NEC 310.15 2. NEED MINIMUM #10 CU GROUND TO J-BOX ENCLOSURE - 250.122 3. PANEL DIRECTORY TO BE CORRECT & LEGIBLE - NEC 408.4 4. USE STRUT & CLAMPS FOR MAST ABOVE PANEL - WOOD & LAGS NOT HOLDING - WOOD WILL ROT - NEC 230 |