Permit: T07EL01894

Parcel: 127081810


Addresses:

5418 E 10TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN WORKING CLEARANCES 110.26
2. MAINTAIN 3' CLEARANCE GAS REGULATOR
3. PANEL SCHEDULE TO BE AS PER 408.4 - NO ABBREVIATIONS OR GENERAL LABELING
4. TIGHTEN LOOSE FITTINGS
5. NM CABLE IMPROPERLY INSTALLED TO BACK SHED
6. FINISH DRIVING GROUND RODS FLUSH
7. PLEASE VERIFY PERMIT FOR NEW A/C UNIT