Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 10/30/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. RISER CONDUCTORS NOT INSTALLED YET 2. BOND GAS PIPING |
|
| 10/26/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY CLAMP RISER TO BRACE SUPPORTS 2. STRAP #4 BARE COPPER WIRE TO WALL 3. YOU WILL NEED A WEATHERPROOF J-BOX FOR SPLICING BRANCH CIRCUITS 4. TWO GROUND RODS REQUIRED 6' AWAY 5. USE A ROMEX CONNECTOR WHERE GROUND COMES IN UNDER SERVICE 6. ADDRESS SERVICE |