Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 2. INSTALL ALL STRANDS UNDER TERMINAL LUG 3. SECURE CABLES TO BOX 312.5 4. SHEATHING TO EXTEND 1/4" INTO BOX 5. SUPPORT BOND CONDUCTOR & VERIFY WATER BOND 6. CIRCUIT DIRECTORY TO BE AS PER 408.4 |