Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAST BRACE TO BE USED AS LISTED, NOT WITH THREADLESS CONNECTORS. THREAD INTO FEET AND SECURE INTO STRUCTURE (TRUSSES) NOT JUST INTO ROOF SHEATHING. LUG BOLTS ARE PROVIDED WITH THIS KIT.
2. PANEL COVER IS NOT CLOSING CORRECTLY

OTHER CORRECTIONS OK
10/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
1. BOND GAS TO COLD WATER PIPE, NOT HOT AND SECURE BOND WIRE
2. IDENTIFY PANEL DIRECTORY
3. NEUTRAL TO SUB-PANEL IN SERVICE TO BE WHITE AND INSULATED
4. INSTALL A LISTED GUY KIT FOR SERVICE MAST

NOTE: SERVICE ENERGIZED BEFORE APPROVAL