Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPENING IN BACK OF PANEL WHERE WIRES ENTER PANEL WITH NON-COMBUSTIBLE MATERIAL 2. COULD NOT VERIFY GAS & WATER BOND - NEC 250.104 3. INSTALL ANTI-OXIDATION COMPOUND ON ALL ALUMINUM TERMINATIONS 4. PLEASE VERIFY PERMIT FOR NEW A/C UNIT PLEASE PROVIDE COPY OF PERMIT |