Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A LISTED MAST BRACE - NEC 230 2. GROUNDING ELECTRODE CONDUCTOR TO BE SECURED TO STRUCTURE AND OR BURIED. G.E.C NOT SECURE INSERVICE AND LAYING AGAINST BUSS - NEC 250 3. GROUND RODS TO BE MINIMUM 6' APART - NEC 250 4. IDENTIFY SERVICE NEUTRAL AS IT LEAVES WEATHERHEAD NEC 200 5. CONDUCTORS IN RACEWAY TO ATTIC TO BE PROPERLY DERATED FOR AMPACITY - NEC 310 6. TIGHTEN ALL CONNECTIONS DO NOT ENERGIZE BEFORE APPROVAL |