Permit: T07EL01871

Parcel: 126121630


Addresses:

4516 E 8TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED TO CHECK GFCI AT BATHROOMS SHOWING OPEN GROUND AND WILL NOT TEST
2) PLEASE GIVE INSPECTION BACK TO DOUG WALKER WHEN RECALLED
07/14/2008 ELECTRIC - FINAL Denied NO ANSWER AT DOOR - RANG DOORBELL
RECALL INSPECTION
01/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH PREVIOUS ITEMS
OK TO CLOSE LAUNDRY WALL
11/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HIGHEST BREAKER TO BE 6'9"
2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
4. LABEL BREAKERS AS PER 408.4 - NO GENERAL LABELING
NO ABBREVIATIONS
5. GROUND NEW SWITCHES - 406.9
6. USE APPROVED BOX ENTRANCES - 110.3
7. BOXES MORE THAN 1/4" FROM SURFACE - 314.20
8. PLEASE OPEN WALLS AT NEW WIRING TO INSPECT
9. FILL UNUSED OPENINGS IN BOX 110.12
10. INSTALL ALL COVER PLATES