Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO CHECK GFCI AT BATHROOMS SHOWING OPEN GROUND AND WILL NOT TEST 2) PLEASE GIVE INSPECTION BACK TO DOUG WALKER WHEN RECALLED |
|
| 07/14/2008 | ELECTRIC - FINAL | Denied | NO ANSWER AT DOOR - RANG DOORBELL RECALL INSPECTION |
|
| 01/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS OK TO CLOSE LAUNDRY WALL |
|
| 11/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HIGHEST BREAKER TO BE 6'9" 2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 4. LABEL BREAKERS AS PER 408.4 - NO GENERAL LABELING NO ABBREVIATIONS 5. GROUND NEW SWITCHES - 406.9 6. USE APPROVED BOX ENTRANCES - 110.3 7. BOXES MORE THAN 1/4" FROM SURFACE - 314.20 8. PLEASE OPEN WALLS AT NEW WIRING TO INSPECT 9. FILL UNUSED OPENINGS IN BOX 110.12 10. INSTALL ALL COVER PLATES |