Permit: T07EL01859

Parcel: 12704245A


Addresses:

5023 E 5TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01859

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE CANNOT BE EXPOSED WHERE RUN DOWN WALL TO RECEPTACLES, ALSO, ROMEX RUN INTO SUB-PANEL
2. LABEL SERVICE EQUIP. WITH ADDRESS
3. DOUBLE LUGGING OF LOAD CONDUCTORS IN SERVICE DISCONNECT NOT ALLOWED
4. PROVIDE ROOF ACCESS