Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2008 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 12/14/2007 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSSOVER |
|
| 12/11/2007 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection :* 1. A PERMANENT METAL ADDRESS LABEL IS NEEDED 2. A 2ND GROUND ROD IS NEEDED 6' AWAY FROM 3. USE APPROVED CLAMP WITH GROUND ROD 4. DRIVE GROUND RODS FLUSH WITH GRADE 5. SECURE GROUNDING CONDUCTOR TO STRUCTURE OR/AND BURY 6. SECURE CABLES TO JUNCTION BOX 7. VERIFY JUNCTION BOX FOR FILL CAPACITY 8. DERATE CONDUCTORS IN RACEWAY PER 310.15 |