Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01844
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
10/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CHECK MAKE UP IN PANEL, HAVE ONE NEUTRAL FOR THREE BRANCH CKTS? HAVE BLACK & YELLOW CONDUCTORS TO NEUTRAL BAR? HAVE WHITE TAPED BLACK? 2. PANEL DIRECTORY TO BE CORRECT, LEGIBLE DO NOT ABBREVIATE 3. CKT ENTERING BACK OF PANEL TO BE MADE RAINTITE 4. USE PIPE CLAMP TO GAS, NOT REBAR CLAMP 5. SECURE CONDUCTOR TO WALL GOING TO WATER BOND |
|
10/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |