Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ADD ALL NEW INTERIOR WIRING TO PERMIT FOR INSPECTION 2. INSTALL A LISTED MAST BRACE 3. SEAL ROOF FLASHING 4. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES 5. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH 6. NEED GFI PROTECTION AND WEATHERPROOF COVER & BOX FOR WASHER RECEPTACLES 7. NEED WEATHERPROOF COVER FOR DRYER RECEPTACLES & BOX 8. MISSING L.B COVER UNDER SERVICE 9. RE-ATTACH PHONE/CATV GROUNDS PARTIAL INSPECTION |