Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BARE CONDUCTOR ON OLD SERVICE CABLE IS NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR TO BE SIZED PER 220.61 FOR FEEDERS & IDENTIFIED PER NEC 200.6 INSTALL NEUTRAL CONDUCTOR TO OLD FEEDER |