Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO BOND GAS & WATER PER NEC 250.104 & 250.66, 250.122 2. CANNOT USE CHASE NIPPLE FOR CONNECTION OF LB TO PANEL. USE LOCK NUT WITH CHASE NIPPLE - NEC 110.3 |