Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEM #1 & #2 FROM PREVIOUS INSPECTION 2) RECALL WHEN READY ANS SWING OVER COMPLETE |
|
| 10/15/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT VERIFY GAS & WATER BOND. SIZE WTR BOND PER NEC 250.104 & 250.66 2. PROPERLY INSTALL GROUND CLAMP AT WATER PIPE 3. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING SURFACE 4. COMPLETELY DRIVE LUG BOLTS ON 2 HOLE STRAP 5. PROVIDE CLEAR WORKING SPACE IN FRONT OF PANEL 30" WIDE X 36" DEEP 6. RECALL WHEN READY |