Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SEAL OPENING IN BACK OF PANEL WERE WIRES COME THRU WITH NON COMBUSTIBLE MATERIAL 2) MAX # OF WIRES TO BE TERMINATED ON LARGER TERMINAL OPENINGS FOR GROUNDING IS 3 #14 OR 3 #10 SE PANEL COVER 3) RECALL WHEN READY 4) GAS AND WATER BOND OK. GROUND RODS OK |