Permit: T07EL01821

Parcel: 136080770


Addresses:

9601 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/14/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS & WATER PER NEC 250
2. FINISH GROUND RODS
3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
4. INSTALL BONDING BUSHINGS ON RISER & NIPPLE FROM METER TO PANEL
5. INSTALL PROTECTIVE BUSHING AROUND WIRES THROUGH BACK OF PANEL
6. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL
7. NEED PANEL DIRECTORY
8. MARK SERVICE DISCONNECT
9. WORK NOT COMPLETE THIS MAY NOT BE COMPLETE LIST