Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAS & WATER PER NEC 250 2. FINISH GROUND RODS 3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 4. INSTALL BONDING BUSHINGS ON RISER & NIPPLE FROM METER TO PANEL 5. INSTALL PROTECTIVE BUSHING AROUND WIRES THROUGH BACK OF PANEL 6. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 7. NEED PANEL DIRECTORY 8. MARK SERVICE DISCONNECT 9. WORK NOT COMPLETE THIS MAY NOT BE COMPLETE LIST |