Permit: T07EL01812

Parcel: 108201000

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01812

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/22/2007 ELECTRIC - FINAL Approved
10/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY PANEL DIRECTORY
2. MULTIPLE/DIFFERENT SIZED EQUIPMENT GROUNDS IN PANEL NOT TO BE UNDER SAME SET SCREW, TIGHTEN ALL CONNECTIONS
3. SMOKE DETECTORS TO BE MINIMUM 36" FROM HVAC VENTS
4. PROVIDE ADDITIONAL INFORMATION CONCERNING REMOVED POWER CORD

THERE WILL BE A FEE IF ALL NOT CORRECT NEXT INSPECTION
10/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 30 AMP CORD CAP STILL NOT WIRED CORRECTLY, MISSING GROUND & PROPER CONDUCTOR. WHAT DOES THIS CORD SUPPLY?
2. SMOKE DETECTORS TO BE INSTALLED PER MANUFACTURES INSTRUCTIONS
3. NEW PANEL NEEDS THE ORIGINAL SCREWS IN IT SO I CAN OPEN FOR INSPECTION
10/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SMOKE DETECTORS PER INSTRUCTIONS IN EACH BEDROOM AND HALLWAY
2. INSTALL ALL DEVICE COVERS
3. PROVIDE GFI PROTECTIN FOR KITCHEN AND BATHROOM RECEPTACLES
4. REPLACE ALL CRACKED OR PAINTED OVER DEVICES
5. HAVE 30 AMP CORD CAP AT SERVICE WITH OPEN WIRING
WHAT DOES CORD SUPPLY?
6. INTERIOR PANEL MISSING ITS PROPER COVER
10/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ACCESS TO INTERIOR/DOOR LOCKED