Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAS & WATER PER NEC 250.104 2. NEED PANEL SCHEDULES NEC 408.4 3. ENSURE HAVE GROUND RETURN PATH ON RANCE CIRCUIT TO UNIT #1 4. NEED PROPER SIZE BREAKER FOR RANGE CIRCUIT TO UNIT #1 5. OK GROUND RODS |