Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED COMPLETE PANEL DIRECTORY - NEC 408.4 2. GROUND 2 GANG BELL BOX ON ROOF WITH LARGEST GROUNDING CONDUCTOR INSTALLED - NEC 250.122 & 250.148 3. BLANK OPEN KNOCKOUT BOTTOM OF PANEL - NEC 110.12 |