Permit: T07EL01806

Parcel: 136250850


Addresses:

6625 E NELSON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED COMPLETE PANEL DIRECTORY - NEC 408.4
2. GROUND 2 GANG BELL BOX ON ROOF WITH LARGEST GROUNDING CONDUCTOR INSTALLED - NEC 250.122 & 250.148
3. BLANK OPEN KNOCKOUT BOTTOM OF PANEL - NEC 110.12