10/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL NEW OUTDOOR LIGHTING NEEDS TO BE PERMITTED AND INSPECTED
2. CLEAR ITEMS FROM IN FRONT OF SERVICE TO ALLOW ACCESS
3. NEUTRALS & GROUNDS TO BE SEPARATE AT PANEL
INSTALL SEPARATE GROUND BAR. DO NOT TERMINATE GROUNDS ON NEUTRAL BAR.