Permit: T07EL01792

Parcel: 135050200


Addresses:

6460 E CALLE LUNA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
NEC 110.3
2. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT AND MINERALLAC STRAP - NEC 230.28
3. DO NOT USE NEUTRAL CONDUCTOR FOR GROUNDING OF 2 GANG BELL BOX
4. OK GROUND RODS
5. OK GAS, WATER BOND