Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 10/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE EXPOSE GROUND RODS TO VIEW 2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICE 3. GROUNDING CONDUCTOR IN RACEWAY TO BE GREEN ENTIRE LENGTH 250.119 4. INSTALL ALL STRANDS UNDER TERMINAL LUG 5. USE CORRECT BREAKER AMPACITY TO CONDUCTOR SIZE 6. A PERMANENT METAL ADDRESS LABEL IS NEEDED |