Permit: T07EL01782

Parcel: 133411500


Addresses:

9516 E 3RD ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
10/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE EXPOSE GROUND RODS TO VIEW
2. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICE
3. GROUNDING CONDUCTOR IN RACEWAY TO BE GREEN ENTIRE LENGTH 250.119
4. INSTALL ALL STRANDS UNDER TERMINAL LUG
5. USE CORRECT BREAKER AMPACITY TO CONDUCTOR SIZE
6. A PERMANENT METAL ADDRESS LABEL IS NEEDED