Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE CUT STRANDS ON AC CONDUCTORS 2. COMPLETE ITEM #6 FROM INSPECTION ON 10/2/07 3. ARE CONDUCTORS TO EXISTING PANEL #4 OR LARGER CANNOT SEE WIRE SIZE MARKING IF SO, NEED PROTECTIVE BUSHING. 4. PLEASE VERIFY PERMITS FOR INTERIOR WORK. THIS INSPECTOR HAS SEEN WORK INSIDE HOME THAT REQUIRES PERMITS & INSPECTIONS. THIS NEEDS TO BE TAKEN CARE OF BEFORE NEXT REINSPECTION OR A REINSPECTION FEE WILL NEED TO BE PAID. |
|
| 10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 2. PLEASE VERIFY PERMIT FOR NEW AC UNIT 3. WHAT OTHER WORK (ELECTRICAL) IS BEING DONE 4. PLEASE EXPLAIN OLD 1" EMT WITH WIRES HANGING OUT OF LB NOT CONNECTED TO PANEL 5. LABEL BREAKERS IN PANEL - NEC 408.4 6. HAVE AVAILABLE CIRCUIT BREAKER POSITIONS HIGHER THAN 6'7" - NEC 404.8 7. PLEASE VERIFY PERMITS FOR INTERIOR WORK |