Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119 2. SAME WITH NEUTRAL - ONLY WHITE - NEC 200.6 3. BRANCH CKT'S IN RACEWAY TO BE PROPERLY DERATED FOR AMPACITY - NEC 310.15B2A 4. MAKE SURE EACH BRANCH CKT HAS PROPERLY SIZED EQUIPMENT GROUND & NEUTRAL - NEC 250.122, 200 5. RE-GROUND PHONE/TV TO SERVICE 6. J-BOXES TO BE GROUNDED 7. DRYER TO BE 4-WIRE RECEPTACLE |