Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LOAD CONDUCTORS NOT TO EXIT THROUGH TOP END WALL
SEE INSTRUCTIONS ON PANEL DOOR - NEC 110.3
2. SECURE EMT SUPPORTS TO ROOF - NEC 358.30
3. INSTALL SUPPORT WITHIN 3' OF LB ON ROOF - NEC 358.30(A)
4. WHERE UNGROUNDED CONDUCTORS ARE CHANGED IN SIZE THE GROUNDED (NEUTRAL) CONDUCTOR SHOULD BE CHANGED ACCORDINGLY
5. VERIFY DERATING OF CONDUCTORS IN 1 1/4" EMT IT APPEARS TO BE MORE THAN 10 CURRECT CARRYING CONDUCTORS WHICH REQUIRES 50% DERATION
NEC 310.15 & 310.16