Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LOAD CONDUCTORS NOT TO EXIT THROUGH TOP END WALL SEE INSTRUCTIONS ON PANEL DOOR - NEC 110.3 2. SECURE EMT SUPPORTS TO ROOF - NEC 358.30 3. INSTALL SUPPORT WITHIN 3' OF LB ON ROOF - NEC 358.30(A) 4. WHERE UNGROUNDED CONDUCTORS ARE CHANGED IN SIZE THE GROUNDED (NEUTRAL) CONDUCTOR SHOULD BE CHANGED ACCORDINGLY 5. VERIFY DERATING OF CONDUCTORS IN 1 1/4" EMT IT APPEARS TO BE MORE THAN 10 CURRECT CARRYING CONDUCTORS WHICH REQUIRES 50% DERATION NEC 310.15 & 310.16 |