Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01746
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 1. OK TO ENERGIZE PANEL 2. INSTALL PROTECTIVE BUSHINGS ON RACEWAYS WITH #4 AND LARGER CONDUCTORS - NEC 300.5 3. ENSURE ALL LOCKNUTS ARE WRENCH TIGHT 4. SECURE CONDUITS WITHIN 3' OF CONNECTION POINTS 5. SEAL OPEN KNOCKOUTS 6. RECALL WHEN READY RECEIVED MONEY ORDER #57153882830 FOR $216.00 FOR 2 AFTER HOURS INSPECTIONS |
|
09/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/27/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO RE-ENERGIZE MAIN SERVICE 2) RECALL FOR INSPECTION ON NEW PANEL REPLACEMENT BEFORE ENERGIZING 3) ENSURE SWITCH TO PANEL THAT IS BEING REPLACED IS LOCKED OUT 4) RECEIVED CHECK #2262 FROM ARIZONA WIDE ELECTRIC FOR $108.00 |