Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/05/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEM #1 FROM INSPECTION ON 10/2/07 NEC 404.8 2. CANNOT USE SHEETMETAL SCREW FOR CONNECTIONS OF GROUNDS - NEC 250.8 |
|
| 10/02/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BRING UP GRADE SO BREAKER POSITIONS ARE NOT HIGHER THAN 6'-7" 2) OK GROUND RODS 3) OK GAS AND WATER BOND 4) RECALL WHEN ALL WORK COMPLETE |