Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SUBMIT PLANS TO CITY OF TUCSON OF SCOPE OF WORK FOR APPROVAL |
|
| 11/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BRACKET AROUND MAST THAT COMES WITH MAST KIT. CANNOT USE MINERALLIC STRAP. 2. GROUNDING ELECTRODE CONDUCTOR TOP TO BE CONNECTED TO GROUNDING ELECTRODE CONDUCTOR 3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 4. NEED TO INSTALL SEPARATE SERVICE FOR LAUNDRY ROOM 5. FULL PERMIT FOR ADDRESS 2730 - NEW FEEDER NEEDS TO BE INSTALLED TO 2730 - INSTALL NEW DISCONNECT & GROUNDING ELECTRODE SYSTEM AT 2730 6. GROUND RODS OK 7. GAS & WATER BOND OK |