Permit: T07EL01738

Parcel: 130171840

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01738

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE APPROVED SET OF PLANS ON JOB SITE
2. LINE TERMINATIONS ARE ONLYH SUITABLE
FOR 60/75 DEG. C -- NEC 110.14/310.16
3. BOND GAS & WATER PER NEC 250.104
10/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 600 AMP SERVICE PROVIDE ENGINEERED PLANS WITH LOAD CALCS
- OK 2 GROUND RODS 3/0 COPPER ELECTRODE CONDUCTOR