Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING JUMPER TO MEYERS HUB NEC 250.92 & 250.102 2. PLEASE COMPLETE ALL CORRECTION ITEMS FROM RECONNECT INSPECTION ACTIVITY 3. HOUSE PANEL IS NOT PART OF THIS ACTIVITY AND WILL NOT BE CLEARED. |
|
| 11/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING MEYERS HUB ON LINE SIDE OF SERVICE NEC 250.102 2. NEUTRALS & GROUNDS TO BE SEPARATE AFTER SERVICE DISCONNECT - NEC 250.24 INSTALL GROUND BAR AT HOUSE PANEL 3. HOUSE PANEL IS NOT ON THIS ACTIVITY |