Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALLED PHONE# ON MESSAGE SEVERAL TIMES - KEPT GETTING MESSAGE THAT CRICKET CUSTOMER WAS NOT AVAILABLE. 2. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 3. INSTALL LOCKNUT ON CHASE NIPPLE IN PROPER DIRECTION SO TEETH ON LOCKNUT DIG INTO BOX 4. PROVIDE PERMIT FOR UNIT 4604 UPGRADE & SCHEDULE INSPECTION WITH 4602 5. RECALL WHEN READY |
|
| 10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REVISE PERMIT OR PULL 2ND PERMIT FOR 4604 2. BLANK OPEN KNOCK OUT BOTTOM OF PANEL - NEC 110.12 3. PANEL DIRECTORY PER NEC 408.4 4. BARE CONDUCTOR TO EXISTING PANEL IS NEUTRAL CONDUCTOR & TO BE MARKED & TREATED AS NEUTRAL. NEC 200 & 200.6, 200.7 5. NEUTRAL CONDUCTORS #6 & SMALLER TO BE MARKED ENTIRE LENGTH NEC 200.6 6. #8 AWG CONDUCTOR NOT RATED FOR 60 AMP NEC 110.4, 310.16 7. USE APPROVED CONNECTOR AT 3/4" LB CONNECTION TO JUNCTION BOX NEC 110.3 8. GROUNDING CONDUCTOR CONNECTION TO JUNCTION BOX TO BE BY LISTED MEANS NEC 250 9. INSTALL LOCKNUT ON CONNECTOR IN BACK OF JUNCTION BOX 10. NEED MIN. 6" OF FREE CONDUCTOR LENGTH AT SPLICE POINTS IN JUNCTION BOXES 11. 10/2 ROMEX CANNOT BE USED FOR DRYER CIRCUIT 12. CANNOT USE OPEN CONDUCTORS THROUGH WALLS NOT APPROVED WIRING METHOD 13. REMOVE ELECTRIC TAPE AT WEATHERHEAD CONNECTION TO 1 1/2" EMT INSTALL PROPER SIDE WEATHERHEAD |