Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL01720
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
10/03/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FEEDER TO SUB-PANEL COVERED WITHOUT INSPECTION 2. GROUNDED CONDUCTOR NOT TO MAKE GROUNDING CONNECTION ON LOAD SIDE OF SERVICE DISCONNECT - NEC 250.24 A5, 250.6 A,B 3. PROVIDE LADDER FOR INSPECTION & ACCESS TO INTERIOR 4. VERIFY GROUNDED CONDUCTOR IS BONDED TO SERVICE DISCONNECT ENCLOSURE 250.24C 5. IDENTIFY "SERVICE DISCONNECT" AS SUCH - 230.70B 6. JOB DESCRIPTION SAYS UPGRADE? 7. BOND METAL PIPING TO PANEL/SERVICE 250.104 8. RECONNECT CATV GROUND |