Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07EL01715

Parcel: 113110150


Addresses:

1746 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01715

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2007 ELECTRIC - SERVICE UPGRADE Approved
09/25/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) BOND GAS & WATER PIPING TO SERVICE NEC 250.104
2) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE
3) GROUND RODS OK
4) ENSURE MAST BRACING SECURED TO ROOF TRUSS/RAFTER