Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01708
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE GROUND RODS. GROUND RODS TO BE MIN. 6' APART AND DRIVEN NO MORE THAN 45 DEG. ANGLE 2. WHERE IS TIME CLOCK AND CONTACTORS 3. WHERE ARE RECEPTACLES 4. PROVIDE AVAILABLE FAULT CURRENT AS INDICATED IN NOTICE ABOVE 5. TIGHTEN FITTINGS |