Permit: T07EL01705

Parcel: 113094130


Addresses:

1011 E MITCHELL ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ELIMINATE UN-NEEDED DISCONNECT AND MAKE J-BOX
2. PULL A NUMBER 10 CU EQUIPMENT GROUND FROM SERVICE
TO NEW SUB-PANEL AND ADD GROUND BAR
3. RUN A NUMBER 6 CU PHASE CONDUCTOR FROM J-BOX TO SUB-PANEL FOR SECOND PHASE
4. IDENTIFY PANEL DIRECTORY, INSTALL ALL SCREWS