Permit: T07EL01698

Parcel: 120060990


Addresses:

225 E LINCOLN ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
10/11/2007 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
1) JOURNEYMAN ELECTRIC TO MAKE CORRECTION TO RANGE HOOD WIRING
10/10/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
BLD LOCKED 10:30 AM

LEFT MSG. WITH ETA RECALL INSP.
09/24/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
- INSTALL COVER PLATES FOR SWITCHES IN WEST BEDROOM & BY RESTROOM
- RECEPTACLE TO FAR BACK INTO WALL AT WEST BEDROOM, REPAIR IN LIVING ROOM
- SMOKE DETECTORS REQUIRED IN SLEEPING AREA (BEDROOMS)
- INSTALL GFI PROTECTED RECEPTS BY KITCHEN SINK AND BATHROOM
- SPLICE FOR ROMEX WIRING AT WEST ROOF EDGE TO BE IN APPROVED BOX WITH COVER - ALSO, WIRING TO BE RATED FOR OUTDOOR USE
- WIRING IN STORAGE ROOM IN BACK NOT TO CODE
- FRONT FIXTURE BY DOOR NEEDS TO BE RE-SUPPORTED
- SERVICE DEADFRONT COVER MISSING
- PROVIDE LADDER FOR ROOF INSP
- ADDRESS NOT CORRECT
09/20/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
1) DOG IN YARD
2) RECALL INSPECTION AND LOCK UP DOGS