Permit: T07EL01694

Parcel: 128120160


Addresses:

5050 E EASTLAND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/12/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE
10/03/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
NEED COMPLIANCE WITH NOTE #1 LAST INSP
09/27/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT. NEC 230.38
2) BOND TO WATER PIPING NOT SIZED PROPERLY-NEC 250.104 AND 250.66
3) CANNOT VERIFY GAS PIPE BONDING NEC 250.104