Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE |
|
| 10/03/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* NEED COMPLIANCE WITH NOTE #1 LAST INSP |
|
| 09/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT. NEC 230.38 2) BOND TO WATER PIPING NOT SIZED PROPERLY-NEC 250.104 AND 250.66 3) CANNOT VERIFY GAS PIPE BONDING NEC 250.104 |