Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01687

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OK GROUND RODS
2. COMPLETE ITEM #2 FROM PREVIOUS INSPECTION ON 3/4/08 TO AVOID REFEE HAVE COMPLETED BY NEXT INSPECTION
03/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE BOTH GROUND RODS
NEED MIN. 2 RODS MIN. 6' APART
2. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH OF WIRE - NEC 250.119
02/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE GROUND RODS
2. NEED PANEL DIRECTORY - NEC 408.4
3. WHEN UNGROUNDED CONDUCTORS INCREASED IN SIZE EQUIPMENT GROUNDING CONDUCTOR TO BE INCREASED
NEC 250.122