Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OK GROUND RODS 2. COMPLETE ITEM #2 FROM PREVIOUS INSPECTION ON 3/4/08 TO AVOID REFEE HAVE COMPLETED BY NEXT INSPECTION |
|
| 03/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE BOTH GROUND RODS NEED MIN. 2 RODS MIN. 6' APART 2. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH OF WIRE - NEC 250.119 |
|
| 02/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE GROUND RODS 2. NEED PANEL DIRECTORY - NEC 408.4 3. WHEN UNGROUNDED CONDUCTORS INCREASED IN SIZE EQUIPMENT GROUNDING CONDUCTOR TO BE INCREASED NEC 250.122 |