Permit: T07EL01685

Parcel: 106062460


Addresses:

1063 W SIMMONS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE LISTED MAST BRACE - NOT EMT
2. SEAL ROOF FLASHING
3. IDENTIFY NEUTRAL OUT OF WEATHERHEAD
4. NEUTRAL TO SUB-PANEL J-BOX UNDERSIZED - NEED SEPARATE NEUTRAL TO DRYER AND SUB-PANEL
5. MULTIPLE SIZE GROUNDS NOT ALLOWED UNDER SAME GROUND LUG
6. GROUND TO BE GREEN OR BARE ENTIRE LENGTH
7. GROUND RODS TO BE MINIMUM 6' APART AND DRIVEN FLUSH
8. PROVIDE ACCESS TO GAS BOND
9. TIGHTEN ALL CONNECTIONS, FITTINGS, LOCKNUTS
10. RECONNECT TELCO GROUND

WORK TO BE DONE BY QUALIFIED ELECTRICIAN