Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LISTED MAST BRACE - NOT EMT 2. SEAL ROOF FLASHING 3. IDENTIFY NEUTRAL OUT OF WEATHERHEAD 4. NEUTRAL TO SUB-PANEL J-BOX UNDERSIZED - NEED SEPARATE NEUTRAL TO DRYER AND SUB-PANEL 5. MULTIPLE SIZE GROUNDS NOT ALLOWED UNDER SAME GROUND LUG 6. GROUND TO BE GREEN OR BARE ENTIRE LENGTH 7. GROUND RODS TO BE MINIMUM 6' APART AND DRIVEN FLUSH 8. PROVIDE ACCESS TO GAS BOND 9. TIGHTEN ALL CONNECTIONS, FITTINGS, LOCKNUTS 10. RECONNECT TELCO GROUND WORK TO BE DONE BY QUALIFIED ELECTRICIAN |